TPI 709R Gas Analyser Kit 1

Product Code: TPI709RKIT1

Price
£509.45 ex. VAT £611.34 inc. VAT

Available In 3-7 Days


Add To Favourites
Detailed Description

DELIVERY SCOPE

Flue gas analysers are ordered back to back from many suppliers. This is due to the degradation that can occur with certain sensor heads that are held on shelves for too long and affects all distributors. We want you to receive the best product with the maximum life efficiency possible, with this in mind please allow for a slightly longer than usual delivery, generally around 4-5 days.

 

All TPI analyzers feature quick and simple set up. Fast purge and the ability to perform fuel selection during start up enable tests to be performed quickly without requiring extra set-up time after initial start up. TPI analyzers also use the last selected fuel as the default setting. This feature prevents the need to perform fuel selection every time the analyzer is turned on

The carbon monoxide sensor used in TPI combustion efficiency analyzers feature an on-board filter capable of filtering NO (nitric oxide), NO2 (nitrogen dioxide) and NOX (combination of NO and NO2) to prevent cross sensitivity errors.

Use TPI analyzers to test flue gases in gas and oil fired equipment including high efficiency furnaces and condensing boilers. Measure CO, O2, and stack temperature. Determine combustion efficiency, CO2, and CO air free. Some models include built-in differential manometer, combustible gas detection, PC communication, data logging, and can measure NO / NOX.

This Kit Contains:

  • TPI 709R Instrument
  • Infrared Printer = 709R Kit 1
  • Rubber Boot (A765)
  • Battery Charger (A766) - 1 each
  • Soft Carrying Case (A768)
  • Flue Sampling Probe (A770)
  • In-Line Filter assembly installed on Flue probe (A794)
  • Temperature Probe (GK11M)
  • Mini Pump Protection Filter Assembly and spare filters (A763)
  • Exhaust Spigot (removable) (A764)
  • Instruction Manual
Model 709R Specifications
 Carbon Monoxide (CO)
 Measurement
 Range 0 to 10,000 ppm
 Resolution 1 ppm
 Accuracy +/-5ppm or 5% of reading whichever is greater
 Oxygen (02) Measurement  Range 0 to 25%
 Resolution 0.1%
 Accuracy ±0.3%
 Carbon Dioxide (CO2)  Range 0 to 25%
 Resolution 0.1%
 Calculated Value
 Nitric Oxide Measurement  N/A
 NOX Measurement  N/A
 Temperature Measurement  Range -40 to 1472°F, or -40 to 800°C
 Resolution 1°F or °C
 Accuracy (K-type) ±0.3%, ±2°F or ±1°C
 Draft/Pressure
 Measurement
 Selectable Ranges mBar,kPa, and inH2O
 Ranges -150 mBar to +150 mBar -15 kPa to +15 kPa -60
 inH2O to +60 in H20
 Resolution 0.001 inH2O
 Accuracy ±0/5% fsd
 Gross/Net Efficiency  Range 0 to 100%
 Resolution 0.1%
 Calculated Value
 CO/CO2 Ratio  Range 0 to 0.999
 Resolution 0.001
 Calculated Value
 Operating Temperature  14°F to 122°F (-10°C to 50°C)
 Battery Type  Rechargeable Batteries
 Selectable Fuels  Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal,
 Anthracite Coal, Coke, Butane, Wood, Bagasse
 Display Type  Backlit 3 line LCD
 Data Storage  50 Locations
 Data Logging  N/A
 Print Capability  Yes, via optional IR printer (A740)
 PC Communication  N/A
 Date and Time Function  24 Hour Real Time Clock
 Dimensions  200mm x 90mm x 60mm
 Weight  500g
 Conformity  BS7927 (and the draft BS7967)
UK Mainland Order by 2pm for Next Day Delivery*
Under £25.00 £4.50
Over £25.00 FREE

UK Highlands & Islands Order by 2pm for Next Day Delivery*
Under £80.00 £15.00
Over £80.00 FREE