Kewtech KT1795 Two Pole Voltage and Continuity Tester

Product Code: KEWKT1795

Price
£68.95 ex. VAT £82.74 inc. VAT

In Stock


Add To Favourites
Detailed Description

Two pole voltage and continuity tester with LCD readout and ghost voltage clearance feature.

KEY FEATURES:

  • AC voltage range 6V - 1000V
  • DC voltage range 6V - 1500V
  • Single pole voltage detection on both probes
  • Phase rotation - Bright green LEDs show left or right rotation
  • Push buttons to increase the testing load to clear ghost voltages
  • 1V LCD resolution display
  • Bright LEDs indicate the voltage level
  • Clear audible tone
  • Bright torch light - gives ample illumination
  • Continuity Test
  • Diode test
  • Self-diagnostic test
  • Polarity indication
  • Auto power on/off
  • Data hold

Two pole voltage and continuity tester with LCD readout and ghost voltage clearance feature.

OVERVIEW:

The new KT1795 two-pole voltage and continuity tester is an essential tool in every electrician's toolbox used for voltage indication and the safe isolation of live circuits. The KT1795 will indicate voltage is present even with no batteries or if the batteries go flat so you can have peace of mind of indication when working with live circuits.

The KT1795 has bright LEDs to show the voltage steps and features an LCD display that provides you with an exact voltage readout to a 1V resolution.

KEY BENEFITS:

  • Required for correct safe isolation procedure
  • Ghost voltage clearance function
  • Permanent UK Specific GS38 Slender probe tips NO NEED to swap ends
  • Fits into recessed terminals such as RCBOs without unscrewing any caps
  • IP64
  • Designed to the new international safety standards IEC 61243-3 & IEC 61010-1
  • Cat IV 600V, Cat III 1000V

Kewtech KT1795 Technical Specification

LED nominal Voltage 12/24/50/120/230/400/690/ 1000V, AC
(40…400Hz), DC(±)
LED tolerances EN 61243-3
ELV indication LED >50V AC, >120V DC
Response time <1s at 100% of each nominal value
LCD Range 6…1000VAC, 1500VDC(±)
LCD Resolution 1V
LCD Accuracy ±3%±3dgt (6…1000Vac/1500Vdc)
LCD Overrange indication "OL” 
Peak current with push buttons, not pressed Is <3.5mA (at 1000V)
Peak current with push buttons pressed Is <300 measurement
Measurement Duty 30s ON, 240s OFF
Single Pole Phase Test
Voltage Range 100…1000V AC (50/60Hz )
Phase Rotation Test
System 170…1000V phase-to-phase,
AC 50/60Hz
Continuity Test
Continuity test range 0…500 kohm + 50%
Resistance measurement 0-1999ohm ±(5% + 10dgt);
Resolution: 1ohm
General
Temperature -5…40°C operation;
-20…70°C storage;
No condensation
Humidity max. 85% RH
Altitude up to 2000m
Overvoltage CAT. III 1000V/ CAT. IV 600V
Standard EN/IEC 61243-3:2014
Pollution Degree 2
Protection IP64
Battery 3V (IEC LR03 1.5V x 2)
Internal battery consumption approx. 80mA