Product Code: CHACA771
Available In 3-7 Days
To secure an installation and ensure that it is non-current-carrying, there is a procedure called Separation which imposes the use of a Voltage Absence Tester.
In the context of work on installations connected to the electricity distribution network, the standards stipulate that the measurements must be performed with the power off to avoid electrical hazards (EN 50110-1 standard, DIN VDE 0682-401, NF C 18-510, etc.). To secure the installation and ensure that it is non-current-carrying, there is a procedure called Separation which imposes the use of a Voltage Absence Tester.
CAT IV 1,000 V Voltage Absence Testers (VATs) Use in extreme conditions: type-S extended climatic class RCD trip testing Digital display Complete integrated Autotest Extended continuity test (R< 2 kΩ, 60 kΩ and 300 kΩ) Two-pole phase-sequence testing with "2-wire method" up to 400 Hz, suitable for isolating transformers and electrical generator sets
The Chauvin Arnoux CA 773 is available here.
Voltage detection takes priority, is automatic, and is indicated by distinct visual and audible signals:
Stray voltages can be detected by pressing two buttons simultaneously (double command) to switch to low impedance mode. Crucial redundant safety: An (Extra-Low Voltage) LED is a redundant safety feature that lights up when the voltage present is higher than the ELV (50 Vac/120 Vdc). The higher the voltage present, the faster it flashes.
You can detect the phase simply by establishing contact with one of the test probes
Simple and quick, the 2-wire phase rotation function with a microprocessor is useful in all circumstances, including on installations powered by an electrical generator set or behind an isolating transformer.
By pressing the continuity button, you can check that the conductors are correctly connected. Continuity (R < 100 Ω) is indicated by a loud, continuous audio signal. In addition, the CA 771 offers an extended continuity test and can be used to display the higher values via 3 thresholds (2 kΩ, 6 kΩ, and 300 kΩ). The CA 773 displays the resistance value directly.
By simultaneously pressing the double command, you can cause a fault current sufficient to trip the RCD to flow through a low-impedance load.
The specifications of the CA 771 and CA 773 mean they can be used for work on all LV electrical networks, whether they are electricity distribution networks or the more specific networks encountered in naval or aviation applications.
The type-S extended climatic class allows use in extreme temperature conditions. This means it offers an operating range from -30 °C to +60 °C for applications such as:
Chauvin Arnoux CA 771 & CA 773 Technical Specification Key Differences | ||
Technical Specifications | CA771 | CA773 |
Display | LEDs | LEDs + backlit digital display |
Voltage |
12 Vac ≤ U ≤ 1,000 Vac 12 Vdc ≤ U ≤ 1,400 Vdc |
|
1.0 V to 299.0 Vac/dc 300 V to 1,000 Vac / 1,400 Vdc |
||
Extended continuity test (resistance) | 2 kΩ, 60 kΩ, 300 kΩ | 0.5 Ω to 2,999 kΩ |
Climatic conditions | -30 °C to +60 °C (Class S) | -15 °C to +45 °C (Class N) |
Battery life | > 5,000 x 10 s measurements | > 2,500 x 10 s measurements |
The CA 753 measurement adapter can be used for measurements in total safety on European 2P+E and Schuko sockets.
Its design guarantees mechanical and electrical contact with all test probes (Ø 2 mm, Ø 4 mm, IP2x, etc.). The presence of a voltage (> 200 V) and the phase position are also indicated.
Removable accessories according to the requirements
Isolated test probes 2 or 4 mm in diameter, IP2X tip protection and test probes.
Chauvin Arnoux CA 771 & CA 773 Technical Specification | ||
Technical Specifications | CA771 | CA773 |
Display | LEDs | LEDs + backlit digital display |
Voltage absence testing (VAT) | ||
Voltage |
12 Vac ≤ U ≤ 1,000 Vac 12 Vdc ≤ U ≤ 1,400 Vdc |
|
1.0 V to 299.0 Vac/dc 300 V to 1,000 Vac / 1,400 Vdc |
||
Frequency | DC, 162/3 to 800 Hz | |
Impedance | > 500 kΩ | |
Max. peak current | 3.5 mA RMS | |
Polarity indication | Yes | |
Redundant hazardous-voltage indication | The ELV (Extra-Low Voltage) LED indicates that the voltage is higher than the SELV (Safety Extra-Low Voltage) with the rate at which it flashes proportional to the voltage level | |
Stray voltage detection | Yes (by low-impedance load switching) | |
RCD tripping | Yes (by low-impedance load switching) (approx. 30 mA at 230 V) | |
Phase/Neutral identification |
Above 50 V (45 - 65 Hz) Above 150 V (162/3 - 45 Hz) |
|
Continuity & Resistance | ||
Buzzer trigger threshold | 100 Ω typical (150 Ω max.) | |
Extended continuity test (resistance) | 2 kΩ, 60 kΩ, 300 kΩ | 0.5 Ω to 2,999 kΩ |
Test current / Open-circuit voltage | ≤ 1 mA / ≤ 3.3 V | |
Phase rotation | 2-wire method with microprocessor | |
Ph/Ph voltage | 50 V ≤ U ≤ 1,000 Vac (45 - 400 Hz) | |
Buzzer |
Intermittent beep for Voltage Detection Continuous beep for continuity |
|
Standards and electrical safety | IEC 61243-3:2009, EN 61243-3:2010, IEC 61010 1,000 V CAT IV | |
Enclosure protection | IP65 | |
Climatic conditions | -30 °C to +60 °C (Class S) | -15 °C to +45 °C (Class N) |
Battery life | > 5,000 x 10 s measurements | > 2,500 x 10 s measurements |
Dimensions / weight | 228 x 60 x 39 mm (without test probes) / 350 g approx. |
Chauvin Arnoux CA 771 & CA 773 Technical Specification Key Differences | ||
Technical Specifications | CA771 | CA773 |
Display | LEDs | LEDs + backlit digital display |
Voltage |
12 Vac ≤ U ≤ 1,000 Vac 12 Vdc ≤ U ≤ 1,400 Vdc |
|
1.0 V to 299.0 Vac/dc 300 V to 1,000 Vac / 1,400 Vdc |
||
Extended continuity test (resistance) | 2 kΩ, 60 kΩ, 300 kΩ | 0.5 Ω to 2,999 kΩ |
Climatic conditions | -30 °C to +60 °C (Class S) | -15 °C to +45 °C (Class N) |
Battery life | > 5,000 x 10 s measurements | > 2,500 x 10 s measurements |
UK Mainland | Order by 2pm for Next Day Delivery* |
---|---|
Under £25.00 | £4.50 |
Over £25.00 | FREE |
UK Highlands & Islands | Order by 2pm for Next Day Delivery* |
---|---|
Under £80.00 | £15.00 |
Over £80.00 | FREE |
Price £256.74 £213.95
Available In 3-7 Days
Price £1192.80 £994.00
Available In 3-7 Days
Price £10302.00 £8585.00
In Stock
Price £277.20 £231.00
Available In 3-7 Days
Price £64.80 £54.00
Available In 3-7 Days