Product Code: MEGRCDT310
Available In 3-7 Days
*Important Calibration Information:
This instrument comes complete with the manufacturer’s calibration certificate. Please be aware that these certificates are generic and may also be time lapsed. If you would prefer a personalised full traceable calibration certificate applied to the equipment before dispatch, then please select this option from the drop-down menu above, an additional calibration charge will apply.
The RCDT330 additionally offers the facility to save test results to internal memory. Over 1000 result can be saved on site, and downloaded to a computer when convenient. Data is stored in non-volatile memory, being retained when the instrument is switched off or batteries are exhausted. A Job reference number can be selected for a range of results, allowing separate locations to be tested with the same tester and easily separated when downloaded. A memory bar graph acts as a ‘Fuel Gauge’ showing how much memory has been used Test results are downloaded to CSV (Comma Separated Variable) spreadsheets, and can be imported into Microsoft Excel®. If certificates or reports are required, the results can be downloaded directly into Megger Powersuite Professional with a range of features for creating professionally finished documentation for NICEIC, ECA BS and other standard formats.
Standard test ranges
Test times for normal and Selective RCDs are:
Normal Selective
1/2I 2s 2s
I 300ms 2s
5I 40ms 150ms
Polarity
Megger RCDT300 Series: RCDT310 RCDT320 RCDT330 | |
RCD Test Ranges (to EN61557-6) | |
Supply Voltage | RCDT310: 100V to 280V (45Hz to 65Hz) RCDT320: 50V to 280V (45Hz to 65Hz) RCDT330: 50V to 280V (45Hz to 65Hz) Minimum voltage 71V for 300mA RCDs, 100V for 500mA RCDs and 205V for 1000mA RCDs |
Test Current Accuracy | |
No Trip Test | (1/2I): -8 to -2% |
Trip Test | (I, 5I): +2% to +8% |
Trip Time | ±1% ± 1ms |
Voltage Measurement | |
AC Range | 0 to 300V (25 to 450Hz) |
Accuracy | ±2% ± 2 digits |
Frequency Measurements (RCDT320/330 Only) | |
Range | 25 to 450Hz |
Accuracy | 25 to 199.9Hz ± 0.1Hz 200Hz to 450Hz ± 1Hz |
Fault (Touch) Voltage | |
Displayed Range | 0 to 50V |
Error | +5%/+15% ± 0.5V |
Programmable RCD Step Increments | |
10mA to 50mA | 1mA steps |
50mA to 500mA | 5mA steps |
500mA to 1000mA | 10mA steps |
Test Result Storage (1000 Results) - RCDT330 Only | |
Job Number | 256 locations |
Distribution Board Number | 99 locations |
Circuits | 99 locations |
Phases | P1, P2, P3 |
Temperature and Humidity | |
Operating Range | -5 to 40°C |
Operating Humidity | 93% RH at +40°C max |
Storage Range | -25 to 70°C |
Maximum Altitude | 2000m |
Environmental Protection | IP54 |
Safety | |
Rating | IEC 61010-1 CAT III 300V phase to earth |
Power Supply | |
Batteries | 8 x 1.5V cells IEC LR6 type (AA alkaline) |
Rechargeable | 8 x 1.2V NiCd or NiMH cells |
Battery Life | 2000 consecutive tests |
General Specs | |
Weight | 980g |
Dimensions | 203 x 148 x 78mm |
E.M.C | In accordance with IEC61326-1 |
UK Mainland | Order by 2pm for Next Day Delivery* |
---|---|
Under £25.00 | £4.50 |
Over £25.00 | FREE |
UK Highlands & Islands | Order by 2pm for Next Day Delivery* |
---|---|
Under £80.00 | £15.00 |
Over £80.00 | FREE |
Price £478.80 £399.00
In Stock
Price £625.20 £521.00
Available In 3-7 Days