The Fluke PRV240FS Proving Unit is a portable, pocket-sized,
battery-powered voltage source. It is specifically built to prove the
functionality of the FieldSense measurement on the T6 electrical
testers. It also provides ac and dc voltages for other HiZ instruments in your tool box.
The Fluke PRV240FS provides a safe method to verify that your T6
electrical tester is operating properly before you conduct any live
tests. The concept of “Test Before Touch” (TBT) involves testing
your T6 against a known live source before and after the actual
measurement. This sequence verifies that your test tool is operating
properly during the actual measurement.
Verify your test tool without unnecessary exposure to shock and
arc flash. Using the PRV240FS reduces the need for personal
protective equipment (PPE) when a known voltage source is not
available for verification of your tester or multimeter before test
before TBT are performed. PPE is still needed for absence of voltage
testing when appropriate.
Specifications | |||
Output voltage | 240 V ac rms or dc | ± 10 % ≥ 1 MΩ | |
LED power indicator | Turns on when output voltage is present | ||
Battery | 4 x AA Alkaline batteries NEDA 15 A IEC LR6 | ||
Battery life | 1100 (10-second duration) test cycles with >1 MΩ load | ||
Operating temperature | -10 °C to +50 °C | ||
Operating humidity | 0 % to 90 % (0 °C to 35 °C) | 0 % to 70 % (35 °C to 55 °C) | |
Operating altitude | 2000 m | ||
Dimensions | 11.7 cm x 7.4 cm x 4.5 cm (4.6 in x 2.9 in x 1.75 in) | ||
Weight | 0.32 kg (12 oz) includes batteries | ||
Safety | IEC61010-1, IEC61010-2-030 | ||
Warranty | One-year | ||
Electromagnetic Compatibility (EMC) | IEC 61326-1: Controlled Electromagnetic Environment CISPR 11: Group 1, Class A Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments. Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. |
||
US (FCC) | 47 CFR 15 subpart B, this product is considered an exempt device per clause 15.103 | ||
Korea (KCC) | Class A Equipment (Industrial Broadcasting & Communication Equipment) Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. |
||