Thanks for adding product ref 775 to compare, click here to compare.
Key Features:
High accuracy measurements +/- 0.2% Volts/Current, 0.3% Energy
Quick set up guide - on screen guides and wiring check
Instantaneous Values
Measures Flicker
Energy consumed
Demand monitor / prediction
Wave form and vector diagrams
Harmonic measurements and analyser
Displays and calculates power factor and corrective capacitors
Includes three 1000A flexi-clamps acurate down to 1A
Print screen function saves any screen, including connection diagram – for fast report writing
Fourth current channel for measured neutral current (neutral current also calculated) or earth leakage
Internal memory plus flash card memory – up to 1GB! Digital output for use to control max demand Two additional inputs for external sensors. For instance to monitor lighting / temperature levels
Ease of use, massive memory, and quick report facility sets this instrument above the competition. Also, there are two analogue input channels, you can monitor any variable for instance watch the change in electrical energy as inside and outside temperature changes - how cool is that!
Overview:
The KEW6315 is our compact power quality analyser with huge testing capabilities, the perfect tool for energy saving, troubleshooting and power quality control.
The KEW6315 enables you to monitor the power quality of a system, altering you to where costs could be saved and where unsafe conditions should be addressed.
Measures data logging, harmonics, waveform and events (transients, dips, swells and interrupts). The tester's large memory also enables you to conduct extended surveys without worrying of running out of storage…we are talking years!
The KEW6315’s quick report facility allows you to download and produce a report in 2 minutes. You can enter daytime and night time tariffs to get the cost of the electricity used. You can even look at a subset of the data i.e. just Monday working hours.
EN 50160 automatic report – again within moments a 17 page report compares the measured data with the supply standard highlighting any errors.
Key Benefits:
Simultaneous measurements; Data logging, harmonics, waveform and events (transients, dips, swells and interrupts) measured all in one go
Extensive memory enables you to conduct extended surveys without the worry of running out of storage
Quick report facility allows you to download and produce a report in 2 minutes and put a cost to energy used
EN 50160 automatic report - again within moments a 17-page report compares the measured data with the supply standard highlighting any errors
Intuitive user interface means that you will soon be up and running and remember the setting up procedure
Remote monitoring on PC and Android devices via Bluetooth
Simultaneous measurements of means that you do not have to do several surveys on the same site
Complies fully to IEC61010-1 CAT IV 300V, CAT III 600V, CAT II 1000V
Includes everything to get you started; KEW6315, three (KEW8130) 1000A flexi-clamps, four voltage test leads, PQA software and SD card
Wiring connections
1P2W, 1P3W, 3P3W, 3P4W
Measurements and parameters
Voltage, Current, Frequency, Active power, Reactive power, Apparent power, Active energy, Reactive energy, Apparent energy, Power factor (cosθ), Neutral current, Demand, Harmonics, Quality (Swell/Dip/Interruption, Transients/Over voltage, Inrush current, Unbalance rate), Capacitance calculation for PF correction unit, Flicker
Voltage (RMS)
Range
600.0/1000V
Accuracy
±0.2%rdg±0.2%f.s.(sine wave, 40~70Hz
Allowable input
1~120% of each range (rms). 200% of each range (peak)
Display range
0.15~130% of each range
Crest factor
3 or less
Sampling speed of Voltage transient
2.4μs
Current (RMS)
Range
8128 (50A type) :5/50A/AUTO
8127 (100A type) :10/100A/AUTO
8126 (200A type) :20/200A/AUTO
8125 (500A type) :50/500A/AUTO
8124/8130 (1000A type) :100/1000A/AUTO
8146/8147/8148 (10A type) :1/10A/AUTO
8129 (3000A type) :300/1000/3000A
Accuracy
±0.2%rdg±0.2%f.s.+accuracy of clamp sensor (sine wave, 40~70Hz)
Allowable input
1~110% of each range (rms). 200% of each range (peak)
Display range
0.15~130% of each range
Crest factor
3 or less
Active Power
Accuracy
±0.3%rdg±0.2%f.s. + accuracy of clamp sensor (power factor 1, sine wave, 40~70Hz)
Influence of power factor
±1.0%rdg (reading at power factor 0.5 against power factor 1)
Frequency meter range
40~70Hz
Power supply (AC Line)
AC100~240V/50~60Hz/7VA max
Power supply (DC battery
Alkaline size AA battery LR6 or Ni-MH(HR15-51)×6 Battery life approx. 3 h (LR6, Backlight OFF)