Megger MTB7671 Calibration Check Box 1002-224

Product Code: MEG1002-224

Price
£398.00 ex. VAT £477.60 inc. VAT

Available In 3-7 Days


Add To Favourites
Detailed Description

Key Features:

• The only one that fully tests your instruments to the regs. 
• Tests the full range of your tester’s capability not just what’s easy
• Won’t trip RCD protected circuits
• Checks insulation, continuity, loop and RCD functions of testers
• Works with all testers for Part P Certification

The Megger MTB7671 instrument test box is produced by Britain’s premier test instrument manufacturer. For that reason it tests your testers to the requirements of British Standards.
Nobody understands the requirements and intentions of the Standards better than Megger, so why waste your money on a lesser product?
Certification bodies like the NICEIC, ELECSA and others now request evidence of your tester’s accuracy and consistency.
The MTB7671 makes that an easy job.

You can test the insulation resistance, continuity, earth loop impedance, PFC, RCD and voltmeter functions of you testers quickly and easily, recording the test results on the record cards included in the pack. There are also self-adhesive test labels for your tester. 

Megger MTB7671 Calibration Check Box
BS7671 & BS EN61557 Tester Requirements MTB7671 Test Parameters Megger Calibration Points
Continuity Short Circuit Test Current >200mA >200mA 
PASS/FAIL indication 
(threshold limits ±2%)
>200mA
Continuity Test Voltage Range 4V - 24V 4V - 24V 
PASS/FAIL indication 
(threshold limits ±2%)
-
Continuity Resistance - 0.5Ω ±3% 0.5Ω
Insulation Test Current 1mA 1mA 
PASS/FAIL indication 
(threshold limits ±2%)
-
Insulation Test Voltages 250V +25% max
500V + 25% max
1kV + 25% max
250V + 25%
500V + 25%
1kV + 25%
PASS/FAIL indication 
(threshold limits ±2%)
-
Insulation Test Resistance 0.25MΩ min
0.5MΩ min
1MΩ min

0.25MΩ ± 3%
0.5MΩ ± 3%
1MΩ ±3%
9MΩ ± 3%
90MΩ ±3%

90MΩ
Loop - Local mains impedance -
Loop + 1Ω - Loop + 1Ω (±5%) 1.0Ω
Loop + 180Ω (IET On-Site Guide 10.3.5 Earth Electrode Resistance) - Loop + 180° (±5%) 180Ω
RCD Currents (I) - 10mA, 30mA and 100mA -
RCD No Trip (1/2 I) No trip >1999ms -
RCD (I) <200ms 40ms @ 0°
50ms @ 180°
-
RCD (5 x I) <40ms 10ms @ 0°
20ms @ 180°
-
UK Mainland Order by 2pm for Next Day Delivery*
Under £25.00 £4.50
Over £25.00 FREE

UK Highlands & Islands Order by 2pm for Next Day Delivery*
Under £80.00 £15.00
Over £80.00 FREE